'CR1000X Series
'Created by Short Cut (4.4)

'Declare Variables and Units
Public BattV
Public PTemp_C
Public Temp_C

Units BattV=Volts
Units PTemp_C=Deg C
Units Temp_C=Deg C

'Define Data Tables
DataTable(Table1,True,-1)
	DataInterval(0,60,Min,10)
	Sample(1,Temp_C,FP2)
	Average(1,Temp_C,FP2,False)
	Minimum(1,Temp_C,FP2,False,False)
	Maximum(1,Temp_C,FP2,False,False)
EndTable

DataTable(Table2,True,-1)
	DataInterval(0,1440,Min,10)
	Minimum(1,BattV,FP2,False,False)
EndTable

'Main Program
BeginProg
	'Main Scan
	Scan(5,Sec,1,0)
		'Default CR1000X Datalogger Battery Voltage measurement 'BattV'
		Battery(BattV)
		'Default CR1000X Datalogger Wiring Panel Temperature measurement 'PTemp_C'
		PanelTemp(PTemp_C,60)
		'Type T Thermocouple measurements 'Temp_C'
		TCDiff(Temp_C,1,mv200C,1,TypeT,PTemp_C,True,0,60,1,0)
		'Call Data Tables and Store Data
		CallTable Table1
		CallTable Table2
	NextScan
EndProg